Portable Three Phase Meter Test System MHTS2.3
Portable Three Phase Meter Test System MHTS2.3
0086-371-60109597
01
Small size and weight, convenient to use at worksite
02
In-built Standard Reference Meter (SRM): accuracy class 0.05
03
Error test, start test, creep test, dial test..etc
04
Measurement of commercial and industrial operations
05
Can be independent set & output of each phase voltage & current
Functions
1) With built-in standard meter class 0.05
2) 7"LCD display
3) Can test and display voltage, current, phase angle, power factor, power, error, active energy, reactive energy, apparent energy, power, phase angle, frequency and etc
4) With enough protection, like short-circuit voltage, current open-circuit protection, overload protection, over-voltage protection
5) 2-31 times harmonics test, adjustable harmonic amplitude (≤40%)
6) Can save test data 500pcs up
7) With two impulse inputs, can get connect with external reference when need, work together with internal error processing system of the unit and then comparing error, through also connecting one power meter
8) With one option for choice between internal reference meter mode or external reference meter mode.
9) Have configuration where you can set the pulse value like pulse/wh or wh/pulse or other
10) Start test/Creep Test/Dial Test
11) RS232 communication port with PC
Technical Index
Accuracy class : 0.05
Voltage range : 10-480V (P-N), 120% adjustable
Current range : 1mA-20A (Current range can be customized according to customer’s requirements)
Supply Voltage : AC 88-284V, 50/60HZ
Power Consumption : 200VA
Ambient Temperature : -10℃-45℃
Influence of auxiliary Voltage : ≤0.005% at 10% Variation
Dimension (approx) : 500*400*188mm
Weight (approx) : 15KG or so
Material of Enclosure : High strength polypropylene composite resin
Frequency Range & Resolution : 45-69HZ, 0.001HZ
Phase Angle Range & Resolution : 0-359.99°, 0.001°
Phase angle Error : 0.03°
Communication Interface : RS232
Voltage Source
Voltage Range (P-N) : 10-480V, 120% adjustable
Internal Ranges/Peak Output Power Value :
Resolution (at final range value) : 0.001 - 0.0001V
Output Accuracy : 0.05%
Distortion Factor : 0.5%
Output Stability : 0.02%/3min
Load Regulation (0-100% load) : 0.02%
Current Source
Current range : 1mA – 20A, 120% adjustable
Internal Range/maximum output power :
Resolution(at final range value): 0.0001 - 0.00001A
Output Accuracy : 0.05%
Distortion Factor : 0.5%
Output Stability : 0.02% / 3min
Load Regulation (0-100% load) : 0.02%
Generation Of Harmonics
Fundamental Frequency Range : 45-69HZ
Harmonics test : 2-51times
Phase shift (basic Waveform/Harmonic) : 0-360°
If you are interested in our products, or if we have anything to help you, you can call our customer service at any time :0371-6010 9597 You can also communicate with us online. Of course, you can also leave a message below, we will be happy to serve you!